![]() |
1800 N.
Glenville Drive, Suite 136 |
Sales / Service Locations |
Backplane / Backpanel
Testing Voltage versus
Insulation Resistance
Voltage Test = Physical Spacing Test (Dielectric Withstanding Voltage - DWV) Our position is that a high voltage test is important. Voltage should be used to test that a minimum spacing between two conductors exists. We recommend that the bare board be tested as high a voltage as economically possible. Current bare board test equipment typically provides test voltages between 100 - 250 volts. With a 250 volt test, you would ensure that exposed conductors have a spacing greater than .005. (Expect to see 50 volts per .001, (.0254 mm), for conductors exposed to air. Soldermask and especially flowed FR-4, prepeg, provide better insulators than air, and therefore provide a much greater voltage per mil. (However, for this discussion, we will focus on external, free air conductors.) The difference in fault coverage between 100 volts, 25 volts and 10 volts is very minimal. (I am of course assuming that dielectric voltage is the issue, not equipment sensitivity). A 100 volt test is at best a .002 spacing test. Our experience is that any sliver or curl that is within .002 of touching another conductive spot represents a very intermittent fault. Thermal expansion of the board, shipment vibration, or just the act of plugging in the daughter card will affect the area. Furthermore, a .003 short would pass test, but could fail after shipment, once the daughter card is inserted, or when the equipment rack warms up. For this reason, our comment is that a 100 volt test is not a true test of physical spacing. Ideally, if slivers and curls are a problem we would recommend voltage testing of 300 volts - 500 volts thereby guaranteeing free air spacing between conductors greater than .006 - .008. (Mil standard 202 defines DWV testing at 500V, 1000V or 1500V). Fortunately, solder slivers and curls have not really been a problem for several years. The technology has matured so that these problems are very rare. Both the bare boards and connectors are built to much more exacting tolerances as well as the skill level of the personnel is much higher than when the technology was in its infancy. To further complicate the voltage testing issue, now that passive and active components are being installed on backplanes, high voltage testing can do significantly more harm than any advantage it may have once offered. When a component is exposed to high voltage, the best case is that it fails immediately. In reality, latent defects are often induced and fail only after some time in functional burn in or once the assembly is placed in the field. When voltage is used as a means to increase the sensitivity of the test equipment another problem can occur. What happens when the board fails? Did it fail due to inadequate spacing or did it fail due to contaminates? The manufacturer may think that there are solder slivers when in reality the boards may be dirty. A .002 spacing fault is almost impossible to verify. Just the act of removing the connector to repair it will alter the slivers spacing. In actuality, if the backplane failed due to spacing, this means that an arc was created. Generating an Arc on a backplane is just as bad and has the same effect as the act of Blowing a short. This is when a high current source is used to melt the conductive material between two traces. (Fortunately, no quality board shop blows shorts anymore.) Both the arc and the blown short leave a significant amount of debris between the two conductors. A common misconception about high voltage testing is that it is current limited, thereby limiting the collateral damage to the backplane assembly. This is not true. The test equipment typically does not provide the current to sustain the arc. The capacitance present on the board sustains the arc. Even if the test equipment charged up the board very slowly, once an arc starts, all of the stored voltage is immediately discharged. The current flowing can be between tens of Amps to hundreds of Amps. There will be carbon tracks and other debris present after an arc. Sometimes the arc will alter the physical characteristics of the conductor and it will now pass a retest, even though debris is now present. This can lead to long-term failure as it provides a medium for Dendritic Crystal growth. Verification of spacing failures can be very frustrating. If it is truly a close spacing failure detected through voltage tests, the verifier must have an instrument with the same voltage capabilities. If they use a standard ohm meter to verify the fault, they will not get any reading. They will be tempted to say it was a false failure as it is not verifiable and will pass the assembly. As a corollary point, if they were able to verify the failure with a standard ohmmeter, then the fault was not a spacing failure to begin with.
Insulation
Resistance Test = Contamination / Cleanliness Test
1. Bare boards should be tested at as high a voltage as economically feasible. 2.
If voltage is truly being used as a method of detecting physical
separation between conductors, the difference between 100 volts and 10
volts is .002 of separation. 3. Solder curls and slivers are almost non-existent with todays mature press fit technology and assembly techniques. 4. Test equipment typically uses voltage to increase its Insulation Resistance sensitivity. 5.
High voltage and components do not mix. 6.
Most voltage failures are actually IR failures. The older test
equipment is made more sensitive by the increased voltage. 7.
Insulation Resistance is a very crucial test as it verifies the
assembly is clear of contaminates. 8. Contaminate detection, (IR Testing), is becoming a major factor in long term assembly reliability as contaminates are directly associated with Dendritic Crystal growth and Conductive Anodic Filament formation. 9.
Sanmina has opted to utilize Analog In-Circuit test equipment to
characterize the quality of todays advanced backplane assembly. 10. Active components are tested using vectorless techniques. (Measure DVf at multiple current levels, or utilize HP TestJet technology.) 11. Series Parallel circuits are testable due to the 6 wire guarded measurement techniques. (Almost all backplanes have pull up / pull down resistor networks which are not testable with anything less than a true In Circuit measurement system) 12. Trace resistance is measurable to .01 ohms on any net with 4 or more test points. (4 wire Kelvin measurement capability) 13.
Insulation Resistance is testable to 100 Mohms. ( 100nAmps @ 10
Volts = 100 Mohms) 14. If active components are present, the test voltage should be .25 volts to preclude any junction damage.
|
Copyright © 1999 Testronics. All rights reserved.
Information subject to change without notice.
Revised: 12/29/03